Eaton Moeller® series DIL-SWD Function element, contactor, SmartWire-DT, DIL/MSC, manual/auto
Product Name |
Eaton Moeller® series DIL-SWD SWD contactor module
|
Catalog Number |
118561
|
Product Length/Depth |
72 mm
|
Product Height |
38 mm
|
Product Width |
45 mm
|
Product Weight |
0.037 kg
|
Certifications |
UL 508
IEC/EN 60947 UL EN 50178 CE CSA File No.: 2324643 CSA Class No.: 3211-07 UL File No.: E29184 IEC/EN 61131-2 UL Category Control No.: NKCR CSA-C22.2 No. 14-05 IEC/EN 60947-4-1 CSA |
Type |
SWD contactor modules
|
Features |
Fieldbus connection over separate bus coupler possible
|
Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Spring clamp connection
|
Fitted with: |
Own supply
|
Number of inputs (digital) |
2
|
Pollution degree |
2
|
Burst impulse |
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3 |
Addressing |
Address set automatically
|
Connection to SmartWire-DT |
Yes
|
Operating mode |
Address allocation via Rotary switch
Control mode |
Category (EN 954-1) |
1
|
Explosion safety category for dust |
None
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Explosion safety category for gas |
None
|
Output current |
0.5 A
|
Current consumption |
40 mA, SmartWire-DT network
|
Voltage type |
DC
|
Mounting position |
As DILM7 to DILM38
|
Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
Overvoltage category |
II
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-30 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
Input current at signal 1 |
3 mA
|
Number of auxiliary contacts |
2
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
Potential isolation |
Connection auxiliary contact: no
|
Cable length |
≤ 2.8 m, Connection auxiliary contact
|
Electromagnetic fields |
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) |
Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
Protocol |
Other bus systems
|
Radio interference class |
Class A (EN 55011)
|
Number of outputs (digital) |
1
|
Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
Pick-up current |
125 mA (for DILM 7-9)
188 mA (for DILM 12-15) 500 mA (for DILM 17-38) |
Connection type |
SWD: Plug, 8-pole
Push in terminals, Auxiliary contact External device plug SWD4-8SF2-5, SmartWire-DT |
Data transmission type |
None
|
Rated operational voltage |
15 V DC (auxiliary contact)
|
Degree of protection |
IP20
|
Station |
SmartWire-DT slave, SmartWire-DT network
|
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Functions |
Display of Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position
For connecting the contactors to SmartWire-DT Contactor actuation |
System accessory |
Yes
|
Terminal capacity |
0.2 - 1.5 mm² (24 - 16 AWG), solid
0.25 - 1.5 mm², flexible with ferrule |
LED indicator |
Status indication of SmartWire-DT network: Green and orange LED
|
Power consumption |
3 W for DILM 7-9 (Pick-up power)
4.5 W for DILM 12-15 (Sealing power) 12 W for DILM 17-38 (Pick-up power) 3 W for DILM 7-9 (Sealing power) 4.5 W for DILM 12-15 (Pick-up power) 0.5 W for DILM 17-38 (Sealing power) |
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Permitted voltage at input - max |
15 V
|
Permitted voltage at input - min |
15 V
|
Permitted voltage at output - max |
28.8 V
|
Permitted voltage at output - min |
20.4 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
0.8 W
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
15 VDC
|
Supply voltage at DC - min |
15 VDC
|
Time delay at signal exchange - max |
84 ms
|
Time delay at signal exchange - min |
10 ms
|
Product category |
SmartWire-DT slave
|
Sealing current |
188 mA, SmartWire-DT network for DILM 12-15
21 mA, SmartWire-DT network for DILM 17-38 125 mA, SmartWire-DT network for DILM 7-9 |