Eaton Moeller® series PKZM4 Circuit-breaker, Ir= 10 - 16 A, Screw terminals, Terminations: IP2X PKZM4-16-CB
Product Name |
Eaton Moeller® series PKZM4 Motor-protective circuit-breaker
|
Catalog Number |
132591
|
Product Length/Depth |
160 mm
|
Product Height |
165 mm
|
Product Width |
55 mm
|
Product Weight |
1.18 kg
|
Compliances |
CE Marked
|
Certifications |
UL 489
CSA CE UL Category Control No.: DIVQ CSA Class No.: 1432-01 UL CSA File No.: 165628 UL File No.: E31593 VDE 0660 CSA-C22.2 No. 5-09 IEC/EN 60947-2 |
Catalog Notes |
Not usable as a main switch
|
Features |
Complete device with protection unit
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Operating frequency |
40 Operations/h
|
Pollution degree |
3
|
Mounting Method |
DIN rail (top hat rail) mounting optional
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Actuator type |
Turn button
|
Adjustment range short-term delayed short-circuit release - max |
0 A
|
Adjustment range short-term delayed short-circuit release - min |
0 A
|
Adjustment range undelayed short-circuit release - max |
224 A
|
Adjustment range undelayed short-circuit release - min |
0 A
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Equipment heat dissipation, current-dependent Pvid |
14.1 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
4.7 W
|
Internal resistance |
29 mΩ
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Altitude |
Max. 2000 m
|
Device construction |
Built-in device fixed built-in technique
|
Connection |
Screw terminals
|
Electrical connection type of main circuit |
Screw connection
|
Lifespan, mechanical |
30,000 Operations (Main conducting paths)
|
Overvoltage category |
III
|
Degree of protection |
Terminals: IP2X
IP20 |
Number of poles |
Three-pole
|
Lifespan, electrical |
30,000 operations (at 400V, AC-3)
|
Terminal capacity (flexible with ferrule AWG) |
14 - 8
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
Functions |
Line and cable protection
For protection of cables and conductors |
Terminal capacity (solid/stranded AWG) |
14 - 6
|
Position of connection for main current circuit |
Other
|
Switching capacity |
16 A, AC-3 up to 690 V
16 A (3 contacts in series), DC-5 up to 250V |
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Overload release current setting - max |
16 A
|
Overload release current setting - min |
0 A
|
Rated frequency - max |
60 Hz
|
Rated frequency - min |
50 Hz
|
Rated operational voltage (Ue) - max |
690 V
|
Rated operational voltage (Ue) - min |
600 V
|
Rated operational current for specified heat dissipation (In) |
16 A
|
Rated uninterrupted current (Iu) |
16 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Stripping length (main cable) |
14 mm
|
Product category |
Motor protective circuit breaker
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated short-circuit breaking capacity Icu at 400 V AC |
65 kA
|
Suitable for |
DIN rail (top hat rail) mounting
Feeder and branch circuit as BCPD, (UL/CSA) |
Short-circuit release |
Basic device fixed 15.5 x Iu
± 20% tolerance 248 A, Irm |
Terminal capacity (solid) |
2 x (0.75 - 16) mm²
1 x (0.75 - 16) mm² |
Rated operational current (Ie) |
16 A
|
Temperature compensation |
-5 - 40 °C to IEC/EN 60947, VDE 0660
≤ 0.25 %/K, residual error for T > 40° -25 - 55 °C, Operating range |
Short-circuit current |
60 kA DC, up to 250 V DC, Main conducting paths
|
Tightening torque |
3.3 Nm, Screw terminals, Main cable
|
Short-circuit current rating (UL 489 CSA 22.2-5.09) |
65 kA, 480 Y/277 V, SCCR (UL/CSA)
22 kA, 600 Y/347 V, SCCR (UL/CSA) |
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 16) mm², ferrule to DIN 46228
2 x (0.75 - 16) mm² |
Power loss |
14.1 W
|