Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 9.5 A, 4 kW, IP66/NEMA 4X, Radio interference suppression filter, Brake chopper, FS2 DC1-349D5FB-A66CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185756
|
Product Length/Depth |
192 mm
|
Product Height |
257 mm
|
Product Width |
188 mm
|
Product Weight |
5 kg
|
Certifications |
Certified by UL for use in Canada
IEC/EN61800-3 EAC RoHS, ISO 9001 UL CE CSA-C22.2 No. 14 RCM UkrSEPRO UL File No.: E172143 Specification for general requirements: IEC/EN 61800-2 UL report applies to both US and Canada CUL IEC/EN 61800-3 UL Category Control No.: NMMS, NMMS7 Safety requirements: IEC/EN 61800-5-1 UL 508C IEC/EN61800-5 |
Catalog Notes |
Environmental class: 3C3, 3S3
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Internal DC link
Breaking resistance Control unit IGBT inverter 7-digital display assembly Radio interference suppression filter Brake chopper PC connection Additional PCB protection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
No
|
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) BLDC motors PM motors Synchronous reluctance motors |
Frame size |
FS2
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-10 °C
|
Mains voltage - max |
480 V
|
Output voltage - max |
500 V
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
6.58 kVA
|
Apparent power at 480 V |
7.9 kVA
|
Application in industrial area permitted |
Yes
|
Heat dissipation details |
Operation (with 150 % overload)
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Switch-on threshold for the braking transistor |
780 VDC
|
Voltage rating - max |
480 V
|
Mounting position |
Vertical
|
Communication interface |
CANopen®, built in
Modbus RTU, built in OP-Bus (RS485), built in SmartWire-DT, optional |
Converter type |
U converter
|
Degree of protection |
NEMA 4X
IP66 |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
5 HP
|
Braking resistance |
120 Ω
|
Equipment heat dissipation, current-dependent Pvid |
136 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 150% overload |
11.5 A
|
Protocol |
MODBUS
Other bus systems CAN EtherNet/IP |
Overload current IL at 150% overload |
14.25 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
Rated operational current for specified heat dissipation (In) |
9.5 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
4 kW
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
8.5 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
7.6 A
|
System configuration type |
AC supply systems with earthed center point
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
100 m, screened, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, Radio interference level, maximum motor cable length C2 ≤ 5 m, Radio interference level, maximum motor cable length 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
2 |
Number of inputs (digital) |
4 (parameterizable, max. 30 V DC)
4 |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
1 (parameterizable, 24 V DC) |
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
96.6 % (η)
|
Supply frequency |
50/60 Hz
50/60 Hz, fLN, Main circuit |
Leakage current at ground IPE - max |
12.6 mA
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
9.5 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
4 kW
|
Output at quadratic load at rated output voltage - max |
4 kW
|
Output frequency - max |
60 Hz
|
Output frequency - min |
0 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
At a switching frequency of 16 kHz and an ambient air temperature of +40 °C
9.5 A at 150% overload |
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|