Eaton Moeller® series MSC-DM DOL starter, 380 V 400 V 415 V: 1.1, 1.5 kW, Ir= 2.5 - 4 A, 24 V DC, DC
Product Name |
Eaton Moeller® series MSC-DM DOL starter
|
Catalog Number |
188261
|
Product Length/Depth |
76 mm
|
Product Height |
170 mm
|
Product Width |
45 mm
|
Product Weight |
0.645 kg
|
Certifications |
UL60947-4-1A
VDE 0660 UL File No.: E123500 CSA-C22.2 No. 14-10 CE CSA CSA Class No.: 3211-04 UL Category Control No.: NKJH CSA File No.: 012528 IEC/EN 60947-4-1 UL |
Type |
Starter with Bi-Metal release
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Short-circuit release
|
Pollution degree |
3
|
Class |
CLASS 10 A
|
Connection to SmartWire-DT |
No
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Model |
IEC/UL starter
|
Altitude |
Max. 2000 m
|
Electrical connection type of main circuit |
Screw connection
|
Voltage type |
DC
|
Mounting method |
DIN rail
|
Overvoltage category |
III
|
Connection |
Screw terminals
|
Functions |
Temperature compensated overload protection
|
Overload release current setting - min |
2.5 A
|
Power consumption (sealing) at DC |
2.6 W
|
Rated conditional short-circuit current (Iq), type 2, 230 V |
50000 A
|
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
50000 A
|
Rated conditional short-circuit current, type 1, 480 Y/277 V |
0 A
|
Rated conditional short-circuit current, type 1, 600 Y/347 V |
0 A
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
4 A
|
Switching capacity (auxiliary contacts, general use) |
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Rated operational current (Ie) |
3.6 A
|
Rated operational voltage |
230 - 415 V AC
|
Suitable for |
Also motors with efficiency class IE3
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Coordination type |
2
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
1
|
Number of command positions |
0
|
Number of pilot lights |
0
|
Overload release current setting - max |
4 A
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
0.75 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
1.5 kW
|
Rated power at 460 V, 60 Hz, 3-phase |
0 kW
|
Rated power at 575 V, 60 Hz, 3-phase |
0 kW
|
Short-circuit release (Irm) - max |
62 A
|
Coordination class (IEC 60947-4-3) |
Class 2
|
Degree of protection |
IP20
NEMA Other |
Electrical connection type for auxiliary- and control-current circuit |
Screw connection
|
Actuating voltage |
24 V DC
|
Power consumption |
2.6 W
|