Eaton Moeller® series Rapid Link - Speed controllers, 4.3 A, 1.5 kW, Sensor input 4, Actuator output 2, 180/207 V DC, Ethernet IP, HAN Q4/2, with manual override switch, with braking resistance, STO (Safe Torque Off)
Product Name |
Eaton Rapid Link Speed controller
|
Catalog Number |
198897
|
Product Length/Depth |
157 mm
|
Product Height |
270 mm
|
Product Width |
220 mm
|
Product Weight |
3.61 kg
|
Certifications |
CE
UL 61800-5-1 IEC/EN 61800-5-1 RoHS UL approval |
Catalog Notes |
|
Features |
Parameterization: drivesConnect mobile (App)
Parameterization: Keypad Parameterization: Fieldbus Parameterization: drivesConnect |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Key switch position AUTO
Key switch position OFF/RESET PC connection PTC thermistor monitoring Breaking resistance Braking resistance Thermo-click with safe isolation Internal DC link Manual override switch Selector switch (Positions: REV - OFF - FWD) Control unit IGBT inverter Key switch position HAND 2 Actuator outputs Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation |
Climatic proofing |
< 95 %, no condensation
In accordance with IEC/EN 50178 |
Operating mode |
Sensorless vector control (SLV)
U/f control BLDC motors Synchronous reluctance motors PM and LSPM motors |
Rated impulse withstand voltage (Uimp) |
2000 V
|
Altitude |
Above 1000 m with 1 % performance reduction per 100 m
Max. 2000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-10 °C
|
Mains voltage - max |
480 V
|
Output voltage - max |
500 V
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Application in industrial area permitted |
Yes
|
Mains voltage tolerance |
380 - 480 V (-10 %/+10 %, at 50/60 Hz)
|
Product category |
Speed controller
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Switch-on threshold for the braking transistor |
765 VDC
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
10 kA
|
Overvoltage category |
III
|
Communication interface |
Ethernet IP, built in
|
Connection |
Plug type: HAN Q4/2
|
Converter type |
U converter
|
Degree of protection |
NEMA 12
IP65 |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
2 HP
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 150% overload |
4.1 A
|
Mains current distortion |
120 %
|
Protocol |
EtherNet/IP
|
Overload current |
For 60 s every 600 s
At 40 °C |
Overload current IL at 150% overload |
6.5 A
|
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
0.75 kW
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
4.3 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
4.3 A
|
System configuration type |
AC voltage
Center-point earthed star network (TN-S network) Phase-earthed AC supply systems are not permitted. |
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Current limitation |
Adjustable, motor, main circuit
0.4 - 4.3 A, motor, main circuit |
Braking torque |
Adjustable to 100 % (I/Ie), DC - Main circuit
≤ 30 % (I/Ie) |
Braking voltage |
280/207 V DC -15 % / +10 %, Actuator for external motor brake
|
Cable length |
C1 ≤ 1 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length C3 ≤ 25 m, maximum motor cable length |
Functions |
4-quadrant operation possible
1 potentiometer speed STO (Safe Torque Off) For actuation of motors with mechanical brake Brake chopper with braking resistance for dynamic braking 3 fixed speeds |
Delay time |
< 10 ms, Off-delay
< 10 ms, On-delay |
Number of inputs (analog) |
0
|
Number of inputs (digital) |
4
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only |
Number of outputs (digital) |
2
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of phases (output) |
3
|
Power consumption |
46 W
|
Interfaces |
Specification: S-7.4 (AS-Interface®)
Number of slave addresses: 31 (AS-Interface®) Max. total power consumption from AS-Interface® power supply unit (30 V): 250 mA |
Efficiency |
98 % (η)
|
Rated control voltage (Uc) |
180/207 V DC (external brake 50/60 Hz)
24 V DC (-15 %/+20 %, external via AS-Interface® plug) |
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
3.5 mA
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
4.3 A
|
Number of HW-interfaces (industrial ethernet) |
2
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
0
|
Output at linear load at rated output voltage - max |
1.5 kW
|
Output at quadratic load at rated output voltage - max |
1.5 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
4.3 A at 150% overload (at an operating frequency of 8 kHz and an ambient air temperature of +40 °C)
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Vibration |
Resistance: 6 Hz, Amplitude 0.15 mm
Resistance: According to IEC/EN 60068-2-6 Resistance: 10 - 150 Hz, Oscillation frequency Resistance: 57 Hz, Amplitude transition frequency on acceleration |
Heat dissipation at current/speed |
32.3 W at 25% current and 0% speed
33.2 W at 25% current and 50% speed 35.2 W at 50% current and 90% speed 36.2 W at 50% current and 0% speed 37.6 W at 50% current and 50% speed 46.3 W at 100% current and 90% speed 48.7 W at 100% current and 0% speed 48.7 W at 100% current and 50% speed |