Eaton Moeller® series PKZM0 Motor-protective circuit-breaker, 0.75 kW, 1.6 - 2.5 A, Feed-side screw terminals/output-side push-in terminals, MSC
Product Name |
Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
|
Catalog Number |
199195
|
Product Length/Depth |
75 mm
|
Product Height |
102 mm
|
Product Width |
45 mm
|
Product Weight |
0.314 kg
|
Certifications |
IEC/EN 60947
VDE 0660 UL File No.: E36332 IEC/EN 60947-4-1 CSA File No.: 165628 UL Category Control No.: NLRV UL CSA-C22.2 No. 60947-4-1-14 CSA Class No.: 3211-05 CSA UL 60947-4-1 CE |
Used with |
Motor starter combinations type MSC...
|
Features |
Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Operating frequency |
40 Operations/h
|
Pollution degree |
3
|
Mounting Method |
DIN rail (top hat rail) mounting optional
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Actuator type |
Turn button
|
Tripping characteristic |
Overload trigger: tripping class 10 A
|
Adjustment range short-term delayed short-circuit release - max |
0 A
|
Adjustment range short-term delayed short-circuit release - min |
0 A
|
Adjustment range undelayed short-circuit release - max |
39 A
|
Adjustment range undelayed short-circuit release - min |
39 A
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
0.5 HP
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
0.17 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
0.5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
1 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
1.5 HP
|
Equipment heat dissipation, current-dependent Pvid |
5.16 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
1.7 W
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Altitude |
Max. 2000 m
|
Device construction |
Built-in device fixed built-in technique
|
Connection |
Push-in terminals on output side
Screw terminals on feed side |
Electrical connection type of main circuit |
Screw-/spring clamp connection
|
Mounting position |
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
|
Lifespan, mechanical |
100,000 Operations
|
Overvoltage category |
III
|
Degree of protection |
IP20
Terminals: IP00 |
Number of poles |
Three-pole
|
Lifespan, electrical |
100,000 operations
|
Shock resistance |
25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
Functions |
Motor protection
Phase failure sensitive |
Terminal capacity (solid/stranded AWG) |
18 - 10, screw terminals
18 - 8, Push-in terminals |
Switching capacity |
2.5 A, AC-3 up to 690 V
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Overload release current setting - max |
2.5 A
|
Overload release current setting - min |
1.6 A
|
Rated frequency - max |
60 Hz
|
Rated frequency - min |
50 Hz
|
Rated operational voltage (Ue) - max |
690 V
|
Rated operational voltage (Ue) - min |
690 V
|
Rated operational current for specified heat dissipation (In) |
2.5 A
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
0.37 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
0.75 kW
|
Rated uninterrupted current (Iu) |
2.5 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Stripping length (main cable) |
12 mm
|
Product category |
Motor protective circuit breaker
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated operational power at AC-3, 440 V, 50 Hz |
1.1 kW
|
Rated operational power at AC-3, 500 V, 50 Hz |
1.1 kW
|
Rated operational power at AC-3, 690 V, 50 Hz |
1.5 kW
|
Terminal capacity (flexible with unisolated ferrule) |
1 x (1 - 6) mm², Screw terminals
2 x (1 - 6) mm², Screw terminals 1 x (1 - 6) mm², Push-in terminals 2 x (1 - 6) mm², Push-in terminals |
Rated short-circuit breaking capacity Icu at 400 V AC |
150 kA
|
Rated short-circuit breaking capacity Ics at 400 V AC |
150 kA
|
Rated short-circuit breaking capacity Icu at 440 V AC |
150 kA
|
Rated short-circuit breaking capacity Ics at 440 V AC |
150 kA
|
Rated short-circuit breaking capacity Icu at 500 V AC |
150 kA
|
Rated short-circuit breaking capacity Ics at 500 V AC |
150 kA
|
Rated short-circuit breaking capacity Icu at 690 V AC |
5 kA
|
Rated short-circuit breaking capacity Ics at 690 V AC |
5 kA
|
Terminal capacity (flexible with ultrasonic welded cable end) |
1 x (1 - 10) mm²
2 x (1 - 6) mm² 1 x (1 - 6) mm², Screw terminals 2 x (1 - 6) mm², Screw terminals 1 x (1 - 10) mm², Push-in terminals 2 x (1 - 6) mm², Push-in terminals |
Suitable for |
Also motors with efficiency class IE3
Branch circuit: Manual type E if used with terminal, or suitable for group installations, (UL/CSA) |
Short-circuit release |
Basic device fixed 15.5 x Iu
± 20% tolerance 38.8 A, Irm |
Terminal capacity (solid) |
1 x (1 - 6) mm², Screw terminals
2 x (1 - 6) mm², Screw terminals 1 x (1 - 6) mm², Push-in terminals 2 x (1 - 6) mm², Push-in terminals |
Rated operational current (Ie) |
2.5 A
|
Temperature compensation |
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40° -5 - 40 °C to IEC/EN 60947, VDE 0660 |
Short-circuit current rating (group protection) |
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA) |
Short-circuit current rating (type E) |
50 kA, 600 Y/347 V, SCCR (UL/CSA)
65 kA, 240 V, SCCR (UL/CSA) 65 kA, 480 Y/277 V, SCCR (UL/CSA) |
Tightening torque |
1.7 Nm, Screw terminals, Main cable
|
Switch off technique |
Thermomagnetic
|
Terminal capacity (flexible with ferrule) |
1 x (1 - 6) mm², Screw terminals
2 x (1 - 6) mm², Screw terminals 1 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-1 2 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-1 1 x (1 - 6) mm², Push-in terminals, ferrule to DIN 46228-4 2 x (1 - 4) mm², Push-in terminals, ferrule to DIN 46228-4 |
Terminal capacity (flexible) |
1 x (1 - 6) mm², Push-in terminals
2 x (1 - 6) mm², Push-in terminals 1 x (1 - 6) mm², Screw terminals 2 x (1 - 6) mm², Screw terminals |
Power loss |
5.16 W
|