Eaton Moeller® series DILM Auxiliary contact module, 4 pole, Ith= 16 A, 3 N/O, 1 NC, Front fixing, Push in terminals, DILM7-10 - DILM38-10
Product Name |
Eaton Moeller® series DILM auxiliary contact module
|
Catalog Number |
199312
|
Product Length/Depth |
54 mm
|
Product Height |
38 mm
|
Product Width |
36 mm
|
Product Weight |
0.05 kg
|
Certifications |
VDE 0660
IEC/EN 60947 CSA File No.: 012528 CSA Class No.: 3211-03 UL File No.: E29184 UL 508 CSA-C22.2 No. 14-05 CE marking UL CSA UL Category Control No.: NKCR |
Catalog Notes |
Rated operational current: Switch-on and switch-off conditions based on DC-13, time constant as specified. Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix F (not N/C late open)
|
Type |
Front mounting auxiliary contact
|
Features |
Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)
|
Electric connection type |
Push-in connection
|
Fitted with: |
Interlocked opposing contacts
|
Pollution degree |
3
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Conventional thermal current Ith at 60°C (3-pole, open) |
16 A
|
Conventional thermal current Ith of auxiliary contacts (1-pole, open) |
0.16 A
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally open contacts) |
3
|
Number of switches (fault signal) |
0
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Mounting method |
Front fastening
|
Connection |
Push in terminals
|
Overvoltage category |
III
|
Control circuit reliability |
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
|
Degree of protection |
IP20
|
Model |
Top mounting
|
Lamp holder |
None
|
Functions |
For standard applications
|
Safe isolation |
400 V AC, Between coil and auxiliary contacts, According to EN 61140
400 V AC, Between auxiliary contacts, According to EN 61140 |
Rated operational current (Ie) |
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series) 3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series) 6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series) |
Lifespan, electrical |
1,300,000 Operations (at 230 V, AC-15, 3 A)
|
Terminal capacity (flexible with unisolated ferrule) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (flexible with ultrasonic welded cable end) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Switching capacity (auxiliary contacts, general use) |
10 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA) |
Switching capacity (auxiliary contacts, pilot duty) |
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA) |
Lifespan, mechanical |
10,000,000 Operations (DC operated)
10,000,000 Operations (AC operated) |
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Number of poles |
Four-pole
|
Short-circuit protection rating without welding |
10 A gG/gL, 500 V, Max. Fuse, Contacts
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
4 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
4 A
|
Rated operational current (Ie) at AC-15, 500 V |
1.5 A
|
Rated operational current (Ie) at DC-13, 110 V |
0.5 A
|
Rated operational current (Ie) at DC-13, 220 V, 230 V |
0.25 A
|
Rated operational current (Ie) at DC-13, 24 V |
2.5 A
|
Rated operational current (Ie) at DC-13, 60 V |
1 A
|
Rated operational voltage (Ue) at AC - max |
500 V
|
Terminal capacity (flexible with ferrule) |
1 x (0.5 - 1.5) mm²
2 x (0.5 - 1.5) mm² |
Terminal capacity (solid) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Terminal capacity (solid/stranded AWG) |
20 - 14
|
Terminal capacity (flexible) |
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm² |
Shock resistance |
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |