Eaton Moeller® series PKZM0 Motor-protective circuit-breaker, 3p, Ir=10-16A, screw connection, large packaging PKZM0-16-GVP
Product Name |
Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
|
Catalog Number |
200524
|
Product Length/Depth |
76 mm
|
Product Height |
93 mm
|
Product Width |
45 mm
|
Product Weight |
0.292 kg
|
Actuator type |
Turn button
|
Adjustment range undelayed short-circuit release - max |
248 A
|
Adjustment range undelayed short-circuit release - min |
248 A
|
Device construction |
Built-in device fixed built-in technique
|
Connection |
Screw terminals
|
Electrical connection type of main circuit |
Screw connection
|
Degree of protection |
IP20
|
Number of poles |
Three-pole
|
Functions |
Phase failure sensitive
|
Overload release current setting - max |
16 A
|
Overload release current setting - min |
10 A
|
Rated operational voltage (Ue) - max |
690 V
|
Rated operational voltage (Ue) - min |
690 V
|
Rated operational power at AC-3e, 220/230 V, 50 Hz |
4 kW
|
Rated operational power at AC-3e, 380/400 V, 50 Hz |
7.5 kW
|
Rated uninterrupted current (Iu) |
16 A
|
Rated short-circuit breaking capacity Icu at 400 V AC |
50 kA
|
Rated short-circuit breaking capacity Ics at 400 V AC |
38 kA
|
Rated short-circuit breaking capacity Icu at 440 V AC |
15 kA
|
Rated short-circuit breaking capacity Ics at 440 V AC |
12 kA
|
Rated short-circuit breaking capacity Icu at 500 V AC |
15 kA
|
Rated short-circuit breaking capacity Ics at 500 V AC |
4 kA
|
Rated short-circuit breaking capacity Icu at 690 V AC |
3 kA
|
Rated short-circuit breaking capacity Ics at 690 V AC |
2 kA
|
Short-circuit current rating (group protection) |
10 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 150 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA) 50 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA) 50 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) 18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA) 18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA) |
Short-circuit current rating (type E) |
65 kA, 240 V, SCCR (UL/CSA) with contactor DILM17
65 kA, 480 Y/277 V, SCCR (UL/CSA) with contactor DILM17 |
Switch off technique |
Thermomagnetic
|
Power loss |
6.43 W
|